Learning Center · Troubleshooting
Solis Inverter Alarm Codes: What NO-Grid, OV-G-V01, ILeak-PRO and the Others Mean
A Solis message is shown on the inverter screen or in the SolisCloud app. NO-Grid means the inverter cannot see the grid (normal in a brownout), OV-TEM means it is too hot, and UN-Vbatt means a low battery. Alarms about leakage, insulation, ground, arcs or reversed polarity (ILeak-PRO, ARC-FAULT, Reve-DC) are safety issues: switch off at the external switches and call your installer. This guide covers the S6 hybrid and grid-tie models, with meanings from Solis’s own manuals and alarm list, and the checks that are safe for an owner.
What do Solis alarm messages mean?
A Solis message is the inverter telling you what it noticed, such as no grid, a battery problem or too much load. Solis shows three kinds: operating status (normal), warnings and alarms. Alarms about leakage, insulation, ground, arcs or reversed polarity are safety issues and need a professional.
| Model in SunTipid’s catalog | Type | Where this page gets the list | Jump to |
|---|---|---|---|
| S6-EH1P3K to 10K-L-PLUS | Hybrid (battery and backup) | Solis S6 hybrid manuals | Hybrid tables |
| S6-GR1P5K | Grid-tie (no battery) | Solis alarm list from its support site | Grid-tie tables |
Which Solis models does this cover?
For the hybrid models we used three Solis S6 hybrid manuals (S6-EH1P8K-L-PLUS, S6-EH1P(3-6)K-L and RHI(3-6)K-S6). They print the same message list. For the grid-tie S6-GR1P we used Solis’s own online alarm list, since we did not find a model manual with a readable table. Both appear in SunTipid’s Solis parts list. The S6-EH1P10K-L-PLUS was not separately checked and the S6-GR1P manual itself was not checked, so treat them as unconfirmed. Solis’s three-phase and larger models are not covered.
How do you restart a Solis hybrid inverter after an alarm?
This is the order in Solis’s S6 hybrid manual. It uses only the external switches:
- Note the message, the time, and what was running.
- Turn off the AC breaker, then the inverter’s DC switch, then the battery breaker. Checking that voltages have dropped to zero is a job for an electrician.
- Wait a few minutes.
- Turn the battery on, then the DC switch, then the AC breaker.
Do not open the inverter. If the same alarm returns after one or two tries, stop and call your installer. Solis says the S6 can power on from solar, battery or grid alone, so it may start even if only one source is present.
S6-EH1P hybrid messages
Operating status messages (not faults)
| Message | What the manual calls it | Plain English | Safe owner-level checks | Call your installer when |
|---|---|---|---|---|
| Off | Control device to shutdown | The inverter has been switched off from its settings. | Turn it on in the ON/OFF setting if you switched it off. | It switches itself off. |
| LmtByEPM | Output is under control | An export limit or meter is capping the inverter’s output. | Nothing to fix if you set an export limit on purpose. | You did not set a limit and output stays low. |
| LmtByDRM, LmtByTemp, LmtByFreq, LmtByUnFr | DRM on; over-temperature, frequency or under-frequency power limit | The inverter is trimming its output for a rule, heat or grid frequency. | The manual says no action is needed. Check ventilation if it is LmtByTemp. | It limits output often. |
| LmtByVg, LmtByVar | Volt-Watt or Volt-Var mode | A grid-code mode that trims output when grid voltage is high. | The manual says this generally needs no action. | Output drops often and you want the setting reviewed. |
| Standby, StandbySynoch, GridToLoad | Bypass run; off-grid to on-grid; grid to load | Normal operating states. | None. The manual says no action is needed. | Not a fault. |
Grid
| Message | What the manual calls it | Plain English | Safe owner-level checks | Call your installer when |
|---|---|---|---|---|
| NO-Grid | No grid | The inverter cannot see the grid. | Check whether Meralco power is out. Look at the AC breaker feeding the inverter: is it on? Wait for the grid to return. | Power is on and the AC breaker is on, but it stays. |
| OV-G-V01, V04, V03, UN-G-V01, UN-G-V02 | Grid voltage above or below the allowed range | The grid voltage is too high or too low for the inverter. | Check whether other appliances show unusual voltage. Wait, then restart the system once. | It repeats often. Ask Meralco about the voltage. |
| OV-G-V02, OV-G-V05, IGFOL-F | Transient grid overvoltage; RMS overvoltage; grid current tracking failure | A short grid spike or a tracking error. | Restart the system once, as the manual says. | It returns. |
| OV-G-F01, OV-G-F02, UN-G-F01, UN-G-F02 | Grid frequency above or below range | The grid frequency is outside the allowed range. | Wait and watch, then restart once. Mostly a grid condition. | It repeats, or the inverter will not restart. |
| G-PHASE, G-F-GLU | Unbalanced grid voltage; grid frequency fluctuation | The grid is unbalanced or unsteady. | Wait and restart once. | It repeats. |
| Surge Alarm | On-site grid surge | The grid had a surge. | Restart the device once. | It stays after a restart. |
Battery and backup output
| Message | What the manual calls it | Plain English | Safe owner-level checks | Call your installer when |
|---|---|---|---|---|
| NO-Battery | Battery is not connected | The inverter cannot see the battery. | Check that the battery is switched on and its breaker is on. Read the battery voltage on the inverter’s info page. Measuring at the plug is for your installer. | It stays. |
| BatName-FAIL | Wrong battery brand selection | The battery model set in the inverter does not match the real battery. | Note the message. Do not change settings yourself. | Always. The setting is for your installer. |
| CAN Fail | Communication with the battery failed | The inverter lost its data link to the battery. | Check that the battery is on. The cable and port checks are for your installer. | It stays. Some batteries need a special cable. |
| OV-Vbatt | Battery overvoltage | The battery voltage is too high. | Switch the system off with the external switches and call. Do not touch battery cables. | Always. |
| UN-Vbatt | Battery undervoltage | The battery voltage is too low. | Restart once, as the manual says. Check the charge level and recharge. | It stays. |
| OV-Vbatt-H / OV-BUS-H | Battery overvoltage hardware failure / VBUS | A hardware overvoltage trip. | Check whether the battery breaker has tripped. Do not reset it more than once. | Always. The manual also says to check if the battery is damaged. |
| OV-Vbackup | Inverting overvoltage | The backup output voltage is too high. | Restart the system once. | It stays. The manual’s wiring check is for your installer. |
| Over-Load | Load overload fault | The backup load is too large, or an inductive load such as a motor starts too hard. | Remove some backup loads and any large inductive load, then restart. | It repeats with light loads. |
Solar panels and leakage
| Message | What the manual calls it | Plain English | Safe owner-level checks | Call your installer when |
|---|---|---|---|---|
| OV-DC01, OV-DC02 | DC 1 or DC 2 input overvoltage | The panel voltage is too high. | Switch off the DC switch and call. Do not measure anything yourself. | Always. |
| DC-INTF. | Abnormal DC input current | The DC input current looks abnormal. | Do not touch cables. Note the message. | Always. The manual points to loose DC connections. |
| OV-DCA-I, OV-DCB-I | DC 1 or DC 2 average overcurrent | Too much DC current on a panel input. | Restart once, as the manual says. | It returns. |
| PV ISO-PRO01, PV ISO-PRO02 | PV negative or positive ground fault | The panel wiring may be leaking to ground, from damaged cable or moisture. | Note the time. Do not touch cables or panels. | Always, if it appears in dry weather or repeats. |
| ILeak-PRO01 to 04, ILeak_Check | Leakage current failures (30 mA, 60 mA, 150 mA and more) and sensor failure | Leakage current to ground was detected. | Restart once. Do not touch anything. | Always. Leakage is a shock risk, so involve a PEE. |
Temperature and internal
| Message | What the manual calls it | Plain English | Safe owner-level checks | Call your installer when |
|---|---|---|---|---|
| OV-TEM | Module over temperature | The inverter is too hot. | Check that nothing blocks the vents and the area is shaded and airy. | It returns, or the heat comes with a smell or discoloration. |
| UN-TEM | Low temperature protection | The inverter is too cold. | Check the working environment temperature, then restart once. | It stays in normal weather. |
| Fan Alarm | Fan alarm | The internal fan may be jammed or not working. | Look and listen from outside. Do not open the case. | It stays. |
| OV-BUS, UN-BUS01, UN-BUS02, UNB-BUS | DC bus overvoltage, undervoltage, abnormal detection or unbalance | Internal power-stage voltage faults. | Restart once. | It returns. |
| OV-G-I, GRID-INTF., GRID-INTF02, DCInj-FAULT | AC overcurrent or grid disturbance; DC component above limit | The grid or AC side looks abnormal. | Check whether the grid is acting up and the AC breaker is on, then restart once. | It returns. The manual’s cable checks are for your installer. |
| RelayChk-FAIL, IGBT-OV-I, 12Power-FAULT | Relay failure; IGBT overcurrent; 12 V undervoltage | Internal faults. | Restart once. | Any returns. |
S6-GR1P grid-tie alarms
These come from Solis’s own online alarm list, which says only trained electricians should diagnose and repair. The numbers in brackets are Solis’s alarm codes.
Grid and meter
| Message | What the manual calls it | Plain English | Safe owner-level checks | Call your installer when |
|---|---|---|---|---|
| NO-Grid (1015) | No grid | The inverter cannot see the grid. | Check whether Meralco power is out and the AC breaker is on. | Power is on and the breaker is on, but it stays. |
| OV-G-V (1010), UN-G-V (1011), OV-G-F (1012), UN-G-F (1013) | Grid voltage or frequency out of range | The grid is above or below the allowed range. | Solis says an occasional alarm may be a short grid event and the inverter resumes by itself. Wait. | It happens often. Solis may need to adjust limits with the utility’s approval. |
| G-PHASE (1016), G-F-FLU (1017), OV-G-I (1018), PHASE-FAULT (101A) | Unbalanced grid, unstable frequency, grid overcurrent, abnormal phase angle | A grid-side problem. | Check whether the grid is acting up, then restart once. | It repeats. Wiring checks are for your installer. |
| Backfeed_Iac (1014), IGFOL-F (1019), INI-FAULT (1031), IG-AD (1047), Vg-Sample (1059) | AC backfeed current, current tracking error, DSP initializing fault, sampling errors | Control or sensing errors inside the inverter. | Restart once. | It returns. |
| GRID-INTF. (1030) | Grid interference | The grid waveform is noisy, for example with several inverters on one line. | Restart once. | It repeats. A filter setting may help, which is for your installer. |
| Failsafe (2010) | EPM communication fail | The inverter lost its link to the export meter. | Check that the meter is powered on. | It stays. |
Solar panels, leakage and arcs
| Message | What the manual calls it | Plain English | Safe owner-level checks | Call your installer when |
|---|---|---|---|---|
| OV-DC (1020), BoostFal (1020), OV-BUS (1021), UNB-BUS (1022), UN-BUS (1023), Vbus-Sam (102A) | DC overvoltage, boost circuit fault, bus voltage faults | The panel or internal DC voltages are abnormal. | Restart once. Do not measure anything yourself. | It returns. Overvoltage needs a technician. |
| DC-INTF. (1027) | Abnormal DC input current | The DC current looks abnormal. | Do not touch cables. Note the message. | Always. Solis points to loose or damaged DC wiring. |
| Reve-DC (1028) | DC reversely connected | A panel string is connected the wrong way round. | Switch off the DC switch and call right away. | Always. Reversed polarity is a fire risk. |
| PV ISO-PRO01 and 02 (1033), PvMidIso (1029), PVGndRun (1029) | Low PV insulation; PV grounded while running | The panel wiring may be leaking to ground. | Solis says alarms in early morning, late afternoon or rain are often normal moisture effects. Note the time. | It appears in dry midday weather or keeps returning. |
| ILeak-PRO (1034), ILeak-Check (1039), L&PE FAULT (F017) | Leakage current protection; self-check; low resistance between L and PE | Leakage to ground was detected. | Restart once. Do not touch anything. | Always. Leakage is a shock risk, so involve a PEE. |
| ARC- FAULT (1041), AFCI-Check (1040) | DC arc detected; AFCI self-check | The inverter suspects an arc in the DC wiring. | Switch off the DC switch and keep away from panel wiring. | Always. Arcs are a fire risk. |
Temperature and internal
| Message | What the manual calls it | Plain English | Safe owner-level checks | Call your installer when |
|---|---|---|---|---|
| OV-TEM (1032) | Over temperature near the IGBTs | The inverter is too hot. | Check for direct sun, blocked vents and a loose mounting. Solis says to turn the inverter off and restart after 15 minutes. | It returns. |
| UN-TEM (103A) | Low temperature | The inverter is too cold. | Check the ambient temperature, then restart once. | It stays in normal weather. |
| RelayChk-FAIL (1035), DSP-B-FAULT (1036), DCInj-FAULT (1037), 12Power-FAULT (1038), IGBT-OV-I (1048) | Relay, DSP, DC injection, 12 V supply and IGBT faults | Internal faults. | Restart once. | Any returns. |
| DSP-SelfCheck (1058) | DSP firmware does not match the hardware | A firmware mismatch. | Note the message. | Always. Firmware is for your installer. |
Warnings
| Message | What the manual calls it | Plain English | Safe owner-level checks | Call your installer when |
|---|---|---|---|---|
| Fan Alarm, Fan_H Alarm | Internal or external fan fault | A fan may be stuck. | Look and listen from outside. Do not open the case. | It stays. |
| DcSpdFail, VgSpdFail | DC or AC surge protector fault | A surge protector failed. | Restart once. | It stays. |
| FuseFail | Fuse alarm (some models) | A fuse alarm on larger models. | Note the message. | Always. |
| Surge Alarm | Grid has surge | A grid surge was recorded. Solis says it does not affect operation. | None. | Not a fault. |
When should you call your installer or a PEE?
- Call right away and keep the system off: any leakage, insulation, ground, arc or reversed-polarity message (for example ILeak-PRO, PV ISO-PRO in dry weather, ARC-FAULT, Reve-DC, OV-Vbatt), or any smell of burning, smoke, heat damage, arcing sounds or water inside equipment.
- Call your installer if it repeats: any alarm that returns after one or two restarts, or any message you do not recognise.
- Involve a PEE: grounding, leakage, insulation or over-voltage problems, and any change to the system. Your installer’s warranty may depend on it.
When you call, have these ready: model and serial number, the exact message and code, the time it started, what was running, and whether it clears by itself. Need an installer? Find installers. Think the system was installed badly? Check our scam guide and Sulit ba? quote checker.
More fault-code guides
Frequently asked questions
What does a Solis alarm like NO-Grid or OV-G-V01 mean?
It is the message the inverter shows on its screen or in the SolisCloud app when it detects a problem. NO-Grid means the inverter cannot see the grid, which is normal during a brownout. OV-G-V01 means the grid voltage is higher than the allowed limit. Find your message in the tables above for its meaning and the checks Solis suggests.
Are messages like LmtByEPM or Standby faults?
No. Solis lists them as operating status messages. They tell you what the inverter is doing, for example limiting its output or waiting. The manual says most of them need no action.
How do I restart a Solis hybrid inverter safely?
Solis’s S6 hybrid manual gives the power-off order: turn off the AC breaker, turn off the inverter’s DC switch, then turn off the battery breaker. To power on, turn the battery on, then the DC switch, then the AC breaker. Checking voltages with a meter is for an electrician. Do not open the inverter.
Is it safe to keep using the system with an alarm showing?
Treat it as a warning and keep it simple. If the inverter has stopped, leave it off and call your installer. Never keep resetting an alarm that returns. Switch everything off and call an electrician right away if you smell burning, see smoke or discoloration, or hear arcing.
Why does my Solis show PV ISO-PRO01 in the morning or after rain?
Solis says low insulation alarms that appear early in the morning, late in the afternoon or on rainy days are often a normal result of moisture in the air. If it appears in dry midday weather or keeps returning, have your installer or a PEE check the panel wiring.
What is the difference between the S6-EH1P and S6-GR1P?
The S6-EH1P is a hybrid inverter with a battery port and a backup output. The S6-GR1P is a grid-tie inverter without a battery. Their alarm lists overlap but are not identical, so use the section for your model.
What if my message is not in this list?
Solis’s lists differ between model families and firmware. This page covers the messages printed in the manuals and Solis’s own alarm list that we checked. If yours is not listed, write down the message, the model and serial number and the date and time, then send them to your installer. Do not guess.
Planning a Solis build?
See which Solis models fit your bill and how many panels they accept.
See Solis invertersOpen the BuilderSources and last checked
Checked November 23, 2026. SunTipid is not a law firm or an engineering firm. This is general information, not legal or engineering advice. Meanings and checks are paraphrased from the sources above in our own words. Always follow the manual that came with your inverter.
- Solis S6-EH1P8K-L-PLUS user manual, section 5 Commissioning and section 7 Troubleshooting (solisinverters.com, November 2024 edition).
- Solis S6-EH1P(3-6)K-L-EU user manual, section 7 (solisinverters.com), used to cross-check.
- Solis Inverter Alarm Codes (Complete List), Solis North America knowledge base, modified April 2025, for the grid-tie alarms.
- SunTipid parts catalog, Solis inverter models.